09-10-2002 - Furniture Gallery AdditionFurniture Gallery Addition
TRC Comments
9/10/02
PLANNING DEPARTMENT
• Per Section 21- 54.03(a)(d), landscaping will be required abutting the 11 additional
parking spaces.
OK
OK
• Per Section 21- 54.03(b) Landscaped area shall be protected from vehicular
encroachment with effective curbs.
BUILDING DEPARTMENT
• The proposed type IV unprotected and unsprinkled building will be classified as
Storage Occupancy (low Hazard) per the Florida Building Code. Table 500 allows
the 10, 306 square foot size. The location to adjoining buildings and the property
line is also allowed by Table 600.
OK
OK
Construction drawings must include the engineered building plans and the
foundation drawings to meet the new Florida Building Code.
ENVIRONMENTAL SERVICES
WATER
N/A
N/A
WASTEWATER
STORMWATER
Being reviewed by Hans Wolfer, Hans to ensure the stormwater pond sizing is sufficient to
meet additional need of addition. Owner will retain maintenance of onsite stormwater
system
FIRE DEPARTMENT
• The required fire flow for this project is 2000 gallons per minute. We will need to
discuss the overall fire flow of this entire site due to additions and growths.
JILL WILL WORK WITH STEVE TO DETERMINE OPTIONS
LEGAL DEPARTMENT
• No comments
CITY ENGINEER
STEVE WILL DISCUSS WITH HANS DIRECTLY.
• More detail is needed on the MES drawing.
• The skimmer detail should show all lumber to be pressure- treated and fasteners to
be '/2" stainless steel log bolts, 4" long, 24 required. (2" x 12" lumber is 11' /z" in
width, not 12" as shown).
• Provide note on plans: Water Retention Areas shall remain as shown unless any
changes are approved by the City Engineer.
• Indicate on the plans the location of the weir and skimmer.
• Need specifications shown on the rip -rap.
• Need computations on the 12" PVC pipe sizes. 12' size appears to be inadequate.
Written response to these comments are required with submittal of seven (7) sets of revised
Site Plans.
While every effort is made to assure that projects reviewed by this office comply with all
applicable codes and standards, we do not certify or guarantee that they do. It is the
responsibility of the applicant to assure compliance with all applicable codes and standards
prior to the project being issued a certificate of occupancy