04-04-2002 - Keith Cope BuildingKEITH COPE BUILDING TRC MINUTES - MEETING 04/04/02 In attendance: Darren Lear, Chief Planner Jill Danigel, Fire Marshall Dennis Fischer, Building Director Pat Drosten, Planning Technician Jeff Gove, P.E., ECT Keith Cope PLANNING DEPARTMENT • Wheel stop are not permitted. Per Section 21- 54.03(b) per the Land Development Code (LDC). Landscaped area must be protected from vehicular encroachment with effective curbs. Curbs will be provided at end of parking and around landscape areas • Impervious area (5,400 sq. ft.) surpasses the St. Johns River Water Management District (SJRWD) threshold (4,000 sq. ft. paved surface), therefore, SJRWMD permit will be required. A copy of the permit must be submitted to the Planning Department prior to the issuance of a Development Order. Permit has been applied for. • Revised Site Plan must show the designated office space to determine the number of parking spaces needed. Office will be approx 12X60. Will show on revised plan. Parking space shown should be adequate. • All new development shall be required to connect to the reclaimed water system, if available, per Section 21- 51.02(c) of the LDC. Note is on landscape plans. Revised landscaping plan must indicate which type of sod will be used, Bahia or Floratam. Will revise. Bahia will be used BUILDING DEPARTMENT The following comments regarding this site plan are derived from the Standard Building Code 1997 edition regarding the future development of this site: • The structure is classified as type IV construction that is unprotected and not protected by an automatic sprinkler system. The total Building coverage will be 2400 square foot. This is a one -story structure and according to Table 500 for business type occupancy, this is acceptable as type IV unprotected and unsprinkled. OK • The separation requirements between each tenant will be determined by the use of each tenant. The minimum separation is one (1) hour but the use may require two (2) hour. Dennis suggests 2 -hour separation be used so as not to limit use if building is subdivided. Construction drawings have been submitted under the Standard Building Code 1997 edition and will be reviewed and inspected under that code section. OK • Interior firewall construction will require footer, no design on plans. Floor will be 6" and will not required footer. ENVIRONMENTAL SERVICES WATER • It is the responsibility of the site developer to provide a reduced pressure backflow prevention device for the potable water service. The device must be installed on the customer side of the meter prior to any branch connections. The device must also be on the approved list maintained by the Environmental Services Administration Office located at 115 East Park Ave. OK Suggestion from Dennis to change water line from 1112 " to 1 ' line. Will show on plans. WASTEWATER • The City will verify the location of the sewer lateral for the builder. However, contrary to the notation on the plans, it is the responsibility of the plumbing contractor on the job to provide the tie -in to the City lateral. OK The City of Edgewater's Environmental Services Department reserves the right to enforce additional requirements as may be necessary to endure compliance with City Codes or other jurisdictional agencies. If you have any questions or require additional information, please contact Terry Wadsworth at 424 -2460. n, FIRE DEPARTMENT • A fire hydrant must be located within 500 feet of the most remote exterior of the building. None is shown on the plans. Will show on plans. The required fire flow for this project is 750 GPM. OK LEGAL DEPARTMENT • No comments CITY ENGINEER • Specifications and details of the mitered -end sections must be shown on the plans. OK. Will show on plans. Written response to these comments are required with submittal of seven (7) sets of revised Site Plans. While every effort is made to assure that projects reviewed by this office comply with all applicable codes and standards, we do not certify or guarantee that they do. It is the responsibility of the applicant to assure compliance with all applicable codes and standards prior to the project being issued a certificate of occupancy