Loading...
10-11-2005 - Florida Casa NetSP 0515— Florida Casa Net Technical Review Committee Minutes October 11, 2005 In Attendance: Jill Danigel, Fire Marshal Brenda Johnson, Dept. Dir. Environmental Svs. Pat Drosten, Planning Technician Jason Kelly, Coldwell Bankers General 1. On Sheet CO -01, notes 20 and 21, remove references to "seeding ". See attached response letter dated October 10, 2005 2. Indicate location and construction material of fence as per the approved variance. See attached response letter dated October 10, 2005 3. Indicate building height on plan. See attached response letter dated October 10, 2005 4. Indicate the elevation and detail of the sidewalk in accordance with City Standard Construction Details. See attached response letter dated October 10, 2005 5. Due to safety concerns regarding visual access to US 1, relocate the proposed sign eastward on the property. See attached response letter dated October 10, 2005 Landscaping 1. Indicate sizes of shrubs and trees in accordance with Sections 21 -54.02 (e) and 21 -21 -55/03 (b). See attached response letter dated October 10, 2005 2. Add a note indicating compliance with Section 21 -54.02 (c). See attached response letter dated October 10, 2005 3. A total of 187 shrubs are required (with a minimum of 38 in the landscape buffer). Several of the proposed shrubs have been determined to be groundcover. Verify acceptable shrub /tree types with City staff. See attached response letter dated October 10, 2005, Per Jill, cabbage palms and saw palmettos are not acceptable trees. Building Department 1. Construction drawings accepted after October 1, 2005 shall comply with the 2004 Florida Building Codes for 120 MPH wind speed within the impact debris region. See attached response letter dated October 10, 2005 2. Provide a letter from the engineer advising that the existing footings are sufficient to accept the additional load of the renovation to the existing building. See attached response letter dated October 10, 2005 Fire - Rescue Department 1. The required fire flow for this project is 500 gallons per minute. See attached response letter dated October 10, 2005 2. The location (and size of water main) of the closest fire hydrant must be indicated on the plans. See attached response letter dated October 10, 2005 SP 0515— Florida Casa Net Technical Review Committee Minutes October 11, 2005 City engineer (David King — Quentin L. Hampton, Associates, Inc.) Vehicle /pedestrian circulation 1. A copy of the FDOT permit for the driveway connection and improvements must be provided. See attached response letter dated October 10, 2005. Will be submitted with revised site plan. Department of Environmental Services 1. According to the survey, the site elevations are assumed. It does not appear that the "assumed" elevations are correct and they should be re- evaluated for accurate construction. See attached response letter dated October 10, 2005 2. With no positive outfall, stormwater design is to be for a 100 - year /3 day storm event in accordance with Section 21 -53.04 (k). See attached response letter dated October 10, 2005. Ok per Brenda. Meets requirements. 3. Areas on the north and west side of the existing building shall be sloped or swaled to allow drainage to the retention areas. Please put flow arrows on the grading plan for clarification. See attached response letter dated October 10, 2005 4. Dumpster enclosure detail needs to be shown on the plans (three sides only — no gate required on the west facing side until such time a dumpster is installed). See attached response letter dated October 10, 2005 5. Commercial water connection in the City of Edgewater are required to install a reduced pressure backflow prevention device on the downstream side of the water meter but prior to the first branch connection. The City of Edgewater Standard Construction Details includes a specific detail for this application. The backflow prevention device must be on the approved list of devices available at the Department of Environmental Services Administration Office located at 115 East Park Avenue or is verifiable by telephone by calling 386 - 424 -2460. See attached response letter dated October 10, 2005 6. On sheet C2 -02: a. Best management practices — the first paragraph should reference the City of Edgewater. See attached response letter dated October 10, 2005 b. Erosion and Sediment Control note #4 — delete reference to Brevard County. See attached response letter dated October 10, 2005 Legal Department 1. The Title Insurance Policy /O &E reflects the following: a. The Commitment is dated July 12, 2005 but the proposed insured is Riverside National Bank, not Florida Casa Net (as the owner). However, the Policy is dated January 31, 2005 with the insured as Florida Casa Net. One or the other should be modified to the correct date or owner. See attached response letter dated October 10, 2005 SP 0515— Florida Casa Net Technical Review Committee Minutes October 11, 2005 b. The Commitment reflects two easements to the City of Edgewater located in OR 641/PG 584 and recorded in OR 669/PG 724 and OR 669/PG 710 — these items must be provided. See attached response letter dated October 10, 2005 c. Staff is unable to locate any easements reflected on the boundary survey — these must be shown See attached response letter dated October 10, 2005