05-23-2006 - Lewis TriplexSP 0608 — Lewis Triplex
Technical Review Committee Minutes
May 23, 2006
Can be shown on landscape plan or signed by engineer
Building Department
1. Construction drawings accepted after October 1, 2005 shall comply with the 2004
Florida Building Codes for 120 MPH wind speed within the impact debris region
and the National Electric Code Edition 2002.
OK
2. Building should be moved forward to the setback line so rear patio slabs could be
installed.
Will show pad with dimensions in rear
Fire - Rescue Department
1. The required fire flow for this project is 750 gallons per minute.
OK
City engineer (David King — Quentin L. Hampton Associates, Inc.)
General provisions
1. Soil report is required.
OK
2. Vicinity plan should include zoning, names of adjoining property owners and
existing land uses.
OK
Utilities
1. Water, sewer and reclaimed water service(s) per City standards should be shown.
OK
2. Individual utility services to serve each unit are recommended.
Will be separate
Vehicle/Pedestrian Circulation
1. Sidewalks should be provided per Section 21- 52.04.
Not required
Stormwater management
1. A grading plan showing existing and modified contour lines should be submitted.
OK
2. A City stormwater permit is required.
Part of building permit
Other
1. Site plan should include or reference all of the applicable City standard
Noted
construction details.
Department of Environmental Services
1. The subject site plan and supporting documentation have been reviewed. The
drawing with the submittal was labeled "architectural site plan" and contained no
water or sewer information. There is water, sewer and reclaimed water available
on India Palm Drive. A fire hydrant is located at 29`" Street and India Palm
SP 0608 — Lewis Triplex
Technical Review Committee Minutes
May 23, 2006
IN ATENDANCE:
Jill Danigel, Fire Marshal
Bonnie Wenzel, Planning Tech
Brenda Johnson, Dept. Dir. — Environmental Svs.
Terry Wadsworth, Dir. — Environmental Svs.
Joffere Lewis
Paula Lewis
Planning Department
General
1. Revise cover sheet to reflect the correct zoning for this parcel: R -4.
OK
2. In order to verify compliance with height requirements, provide building
elevations.
Will provide
Parkin
1. Indicate location of any adjacent driveways.
Will add note: No adjacent driveways
2. Indicate location of any driveways on the west side of India Palm Drive (across
the street from this parcel).
Will add note: No adjacent driveways
3. In the event ownership of the entire building transfers to individual owners, a joint
use driveway agreement is required.
Noted
Landscaping
1. Survey does not indicate location/existence of specimen trees.
On survey, Note 8
2. A total of seven (7) trees are required for the site. Provide dimensions of existing
trees in order to verify if these may be included in total tree count.
Will add
3. Landscape plan must include irrigation plan and indicate compliance with Volusia
County's waterwise ordinance.
OK — reclaimed not available
4. Landscape plan must include language from Section 21 -54.02 (c) "All plant
material used in conformance with the requirements of this Section shall be
Florida grade #1, as established and periodically revised by the Florida
Department of Agriculture and Consumer Affairs ".
Separate Landscape Plan better
5. A Class C buffer is required on the west side of the parcel. This buffer must
include a total of 70 shrubs.
West side abuts alley, will relocate
6. Provide details of compliance with Volusia County tree protection standards (15%
of existing trees must remain on site).
SP 0608 — Lewis Triplex
Technical Review Committee Minutes
May 23, 2006
Drive. Although this is basically a Florida Shores residential unit, more general
site plan information is needed.
Will provide
2. The stormwater calculations and plans prepared by a professional engineer,
registered with the State of Florida, needs to be provided in accordance with
Table V -1, Footnote 10.
Show nearest hydrant on plans